Sales of telecommunication products

Plated steel wire
Steel optical loose tube
Hydrophobic gel
Optical fibreDestination
The corrosion-resistant optical power ground wearer is designed to perform fiber optic lines for overhead power lines of 35 kV and above.
Technical characteristics
| Parameter | Value | ||
| Number of optical fibers | 24 | 48 | |
| Cable diameter, mm | 8,2 | 11,2 | 10,1 |
| Cable weight, kg/km | 244 | 477 | 363 |
| Rated breaking strength (RBS), kN | 44 | 89 | 65,2 |
| Maximum rated design tension (MRDT), kN | 22 | 44,2 | 32,9 |
| SEN, kN | 13 | 27 | 19,5 |
| Sectional area of steel elements, mm2 | 34,4 | 69,3 | 51,3 |
| Whole steel section, mm2 | 36,0 | 70,9 | 53,4 |
| Elasticity modulus (final), kN/mm2 | 116,8 | 119,0 | 117,8 |
| Elasticity modulus (initial, mounting), kN/mm2 | 132,6 | 135,2 | 133,7 |
| Elasticity modulus (exhaust), kN / mm2 | 156,8 | 156,2 | 154,8 |
| Coefficient of linear thermal expansion, 10-6 1/K | 12,0 | 12,3 | 12,7 |
| DC resistance at 20oС, Om/km | 2,449 | 1,232 | 1,644 |
| Thermal withstand (beginning t=250С, final t=2000C), kA2∙s | 6,3 | 25 | 13,9 |
| S/c current for 1 sec, kA | 2,5 | 5,0 | 3,7 |
| Crushing force, kN/sm | 1 | ||
| Operating temperature | -60°С…+85°С | ||
| Installation temperature | -30°С…+50°С | ||
| Transportation and storage temperature | -60°С…+70°С | ||
| Minimum bending radius | Not less than 20 cable diameters | ||
| Factory length, km | 4 | ||
Technical characteristics of optical fiber
| Type of optical fiber | Corning SMF 28 Ultra | Corning SMF28e+BB |
| ITU-T recommendations | G.657A1 G.652D | G.657A1 G.652D |
| Deviation from the concentricity of the core, microns, not more | 0,5 | |
| Diameter of fiber sheath, microns | 125±0,7 | |
| Deviation from the roundness of the sheath, %, not more | 0,7 | |
| The diameter of the protective covering, microns | 242±5 | |
| Maximum attenuation at wavelength 1310 nm | 0,32 | 0,34 |
| Maximum attenuation at wavelength 1550 nm | 0,18 | 0,20 |
Full name example
OPGW-Ts-24-11,2mm-25 kA2∙s-1kN
Cable consist of the central steel loose tube with freely laid fibers. The optical fibers in the loose tube are bundled. Each bundle of fibers has a winding colored synthetic thread. The free space is filled with a hydrophobic gel in the optical loose tube. One lay of reinforcing wires is spirally laid on top.
Download the OPGW-Ts cable specification in PDF
Download the OPGW-Ts cable certificates and declarations in PDF