Sales of telecommunication products
Destination
The corrosion-resistant optical power ground wearer is designed to perform fiber optic lines for overhead power lines of 35 kV and above.
Technical characteristics
Parameter | Value |
Number of optical fibers | Up to 288 |
Cable diameter, mm | 11-21 |
Cable weight, kg/km | 330-1530 |
Rated breaking strength (RBS), kN | 47-275 |
Maximum rated design tension (MRDT), kN | 28-165 |
Elasticity modulus, kN/mm2 | 70-160 |
Thermal withstand, kA2∙s | 5-550 |
S/c current for 1 sec, kA | 4-30 |
Crushing force, kN/sm | 1 |
Operating temperature | -60°С…+85°С |
Installation temperature | -30°С…+50°С |
Transportation and storage temperature | -60°С…+70°С |
Minimum bending radius | Not less than 20 cable diameters |
Factory length, km | 4 |
Technical characteristics of optical fiber
Type of optical fiber | Corning SMF 28 Ultra | Corning SMF28e+BB |
ITU-T recommendations | G.657A1 G.652D | G.657A1 G.652D |
Deviation from the concentricity of the core, microns, not more | 0,5 | |
Diameter of fiber sheath, microns | 125±0,7 | |
Deviation from the roundness of the sheath, %, not more | 0,7 | |
The diameter of the protective covering, microns | 242±5 | |
Maximum attenuation at wavelength 1310 nm | 0,32 | 0,34 |
Maximum attenuation at wavelength 1550 nm | 0,18 | 0,20 |
Full name example
OPGW-C-24-11,2mm-25 kA2∙s-1kN
Cable consist of the central strength element made of aluminum plated steel wire around which is twisted aluminum plated steel wire layer with a steel loose tube with freely laid fibers. The optical fibers in the loose tube are bundled. Each bundle of fibers has a winding colored synthetic thread. The free space is filled with a hydrophobic gel in the optical loose tube. One lay of reinforcing wires is spirally laid on top.
Download the ОPGW-C cable specification in PDF
Download the ОPGW-C cable certificates and declarations in PDF